IFT258 Automatic Burner Control Unit Detection Burner Control System
Technical indexes:
1.Power supply: AC220V±10% 50Hz.
2.Ambient temperature: -20°C ~ +65°C without condensation.
3.Flame detection current: Adjustable between 2-20μA.
4.Protection grade: IP40.
5.Ignition cable: <5m (temperature resisting high-voltage line).
6.Cable length: For electrode ionized detection mode: max 75m; For UV detection mode 100m.
Specifications
Power supply: AC220V
voltage fluctuation scope: -15/+10%
frequency 50HZ
Power: 18VA+25VA
Built-in ignition transformer, with ignition electrode clearance being 2~3mm and ignition high-voltage line <1 m.
The high-voltage line shall not pass through metal pipe and shall separate from the detection line.
Installation sizes:35mm U-shaped rail can be used, width113mm, height 75mm and depth 120mm. Distance between two install ation holes on the base plate is 70mm.
Fuse: 3.15A delay type H.
Detecting mode: both ignition and detection functions are combined into one electrode or two of the electrode separated control.